VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 3 Diagnostics and Troubleshooting
© 19982001 Schneider Electric All Rights Reserved
93
ILF
INTERNAL COMM.
FAULT
Communication fault between the
control board and the option card.
Perform Bus Voltage Measurement procedure
(Procedure 1 on page 87). Check the connection
between the option card and the control board. If the
drive controller has a GPO (General Purpose Option
Card, part number VW3A58253U) installed, see
instruction bulletin 30072-450-03 for troubleshooting
instructions.
InF
INTERNAL FAULT
1. Internal fault.
2. Internal connection fault.
Perform Bus Voltage Measurement procedure
(Procedure 1 on page 87), then check internal
connections.
Ini
Attempting to download an incompatible
file from the keypad display to the drive
controller. Incompatibility can be caused
by dissimilar drive controller part
numbers. Also, incompatibility can occur
when files are created on a drive
controller with new firmware and then
attached to a controller with older
firmware that does not recognize the
new features. The error may appear
after ERR7 is dislayed.
1.Ensure the file being downloaded was created for
the correct drive controller part.
2. Verify drive controller firmware. Reconfigure the
new features used in the newer firmware. Like
configurations are transferable independent of
firmware revision. Another option is to upgrade the
firmware by ordering part number VX4A581U.
Cycle power on the drive controller.
LFF
LOSS OF 4-20 mA
Loss of 420 mA follower signal on AI2
input. See Table 27
1. Verify signal connections.
2. Check signal.
NST
Freewheel Stop
The logic input assigned to NST
(Freewheel stop/Run permissive) is
open.
The drive controller will not run until the logic input
assigned to Freewheel stop / Run permissive is
closed.
ObF
OVERBRAKING
Overvoltage or overcurrent due to
excessive braking or an overhauling
load. See Table 26.
Increase deceleration time. Add dynamic braking
option if necessary, or verify the dynamic braking
option is working properly.
OCF
OVERCURRENT
1. Ramp too short.
2. Inertia too high, or load too large
3. Mechanical blockage.
1. Check the parameter adjustments
2. Check the sizing of the drive controller, motor, and
load.
3. Remove all power. With drive controller
disconnected, check for mechanical blockage.
OHF
DRIVE OVERHEATING
Heatsink temperature too high. Check motor load, fan, and ambient temperature
around drive controller. Wait for drive controller to cool
down before resetting.
OLF
MOTOR OVERLOAD
1. If thermal trip setting meets or
exceeds 118% of the normal thermal
state, thermal trip is due to prolonged
overload or output phase failure.
2. Motor power rating too low for
application.
1. Check setting of Thermal Current (
ItH, see
page 29) and compare with motor I
n
(nameplate
current rating). Check load and compare with
operating speed. Check braking conditions (possibility
of single-phase operation). Wait approximately seven
minutes before resetting.
2. Verify that motor and drive controller selection are
correct for application.
Table 25: Fault Codes and Messages (Continued)
Fault/Message Probable Causes Corrective Actions