
VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 — Menus
© 1998–2001 Schneider Electric All Rights Reserved
65
PID Regulator
This function is used to regulate a process with a setpoint input and a
feedback signal from the process. This function is enabled by assigning
an analog input (AI) to PID feedback in the 5—I/O menu. This function is
available after enabling the Variable Torque Macro and ensuring that the
RFC: Auto/man parameter is not assigned to a logic input. The
acceleration (ACC) and deceleration (dEC) ramps default to linear ramp
type even if the ramps had been configured for S ramp or U ramp with the
rPt parameter.
The PID regulator can be used with a logic input configured for Auto /
Manual mode of operation (also referred to as Reference Switching)
when the Analog option card is used. (Catalog number VW3A58201U)
When the PID regulator is configured and a logic input is configured for
PAU: PID Auto/man, the PID regulator function is active in Auto mode and
AI3 is used for speed input in manual mode.
Logic inputs can be used with the PID regulator to command the drive
controller to run from the analog reference, run at process maximum, or
operate with two other definable pre-set setpoints. The configurable
setpoints can be use to provide two different setpoints for two different
processes, or they can be used in place of using AI1 for setpoint input.
For example, providing a setpoint via the logic inputs can eliminate the
need for a potentiometer.
Four analog outputs are available to monitor various aspects of the PID
regulator function. See pages 73–74 for more information.
Figure 18 shows a diagram of the PID Regulator inputs, calculation
points, and outputs.
Table 20 on page 67 provides a description of the inputs to the PID
Regulator.
PID setpoint OPS PID feedback OPF
PID error OPE PID integral error OPI
Comentarios a estos manuales