VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 — Menus
© 1998–2001 Schneider Electric All Rights Reserved
39
Table 11: 3—Drive Menu Parameters
Parameter Code Description
Adjustment
Range
Factory
Setting
Nom.Mot.Volt- V
UnS
Nominal motor voltage given on the
motor nameplate label.
ATV58••••M2
ATV58••••N4
200 to 240 V
200 to 500 V
230 V or
400/460 V
[1]
Nom.Mot.Freq
- Hz
FrS
Nominal motor frequency given on the
motor nameplate label.
The FrS setting defines the frequency
at which nominal motor voltage (UnS) is
applied to the motor. FrS cannot be set
above the maximum output frequency
setting tFr.
40 to tFr 50/60 Hz
[1]
NomMotCurr.- A
nCr
Nominal motor current given on the
motor nameplate label.
0.25 to 1.36
of I
n
[2]
0.9 of I
n
[2]
Nom.MotSpeed
-rpm
nSP
Nominal motor speed given on the
motor nameplate label.
This should be the value that
incorporates slip (i.e. this value should
be the rpm of the motor when it is fully
loaded).
0 to 9999
rpm
depends on
drive
controller
rating
[1]
Depending on the position of the 50/60 Hz switch. Ensure that the switch setting
matches the input frequency (see page 13).
[2]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[3]
The factory setting depends on the macro-configuration used: No for Material Handling,
Yes for General Use and Variable torque.
[4]
Refer to the drive controller instruction bulletin, VVDED397048US, for duty cycle ratings
of the drive controllers.
★ These parameters are available only with the I/O extension card installed.