VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 — Menus
© 1998–2001 Schneider Electric All Rights Reserved
29
ThermCurrent
-A
ItH
Current setting used for the motor
thermal protection. Adjust ItH to
the nominal current which appears
on the motor nameplate. This
provides Class 20 motor overload
protection.
0.25 to 1.36
of
I
n
[1]
Varies
according
to drive
controller
size.
DC Inj. Time- s
tdC
DC injection braking time. If tdC
= Cont, DC injection is continuous.
0 to 30 s
Cont
0.5 s
Table 6: 2—Fixed Set of Adjustment Parameters (Continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
[1]
I
n
= drive controller constant torque output current rating shown on the drive
controller nameplate.
Menu
2
MOTOR OVERHEATING
• This drive controller does not provide direct thermal protection for
the motor.
• Use of a thermal sensor in the motor may be required for
protection at all speeds or loading conditions.
• Consult the motor manufacturer for thermal capability of the
motor when operated over the desired speed range.
Failure to follow these instructions can result in injury or
equipment damage.
CAUTION
NOTE: DC Inj.
Time is only
available if
automatic DC
injection (AdC) is
set to Yes.