VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 Menus
© 19982001 Schneider Electric All Rights Reserved
41
Max.Freq. - Hz
tFr
Maximum output frequency. The
maximum value is a function of the
switching frequency (SFr, see
page 43).
10 to 500 Hz 60/72 Hz
[1]
Energy Eco
nLd
Optimizes the motor efficiency by
automatically adjusting the Volts/Hz
ratio.
No - Yes Ye s
I Limit adapt.
Fdb
Current limit adaptation. When
configured for Yes, the current limit
setting will increase as a function of
output frequency.
No - Yes No
DecRampAdapt
brA
Activation allows the deceleration ramp
time to be automatically increased,
avoiding an overbraking fault (ObF) if
the ramp time was too short. This
function may be incompatible with ramp
positioning and with dynamic braking.
If relay R2 is assigned to Brake Logic,
brA can only be set to No.
No - Yes No
[3]
SwitchRamp2- Hz
Frt
Frequency for ramp switching. When
the output frequency is greater than Frt,
the ramp times will be AC2 and dE2.
0 to HSP 0 Hz
Table 11: 3Drive Menu Parameters (Continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
[1]
Depending on the position of the 50/60 Hz switch. Ensure that the switch setting
matches the input frequency (see page 13).
[2]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[3]
The factory setting depends on the macro-configuration used: No for Material Handling,
Yes for General Use and Variable torque.
[4]
Refer to the drive controller instruction bulletin, VVDED397048US, for duty cycle ratings
of the drive controllers.
These parameters are available only with the I/O extension card installed.
Menu
3
MACHINERY OVERSPEED
Some motors and/or loads may not be suited for operation above
nameplate motor speed and frequency. Consult motor manufacturer
before operating motor above rated speed.
Failure to follow this instruction can result in injury or equipment
damage.
CAUTION
NOTE: Energy
Eco. is available
only in variable
torque mode.
NOTE: I Limit is
available only in
variable torque
mode.
NOTE: Switch
Ramp 2 is not
available if LI is
assigned to
ramp switching.