VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 Menus
© 19982001 Schneider Electric All Rights Reserved
77
Input Phase
Loss
IPL
Allows activation of the Input Phase Loss fault.
This fault is not configurable on the single
phase input only drive controllers
ATV58U09M2 and ATV58U18M2.
Disable when operating the 208/230 Vac drive
controllers with single phase input.
Yes - No Yes
ThermalProType
tHt This function defines the type of thermal
protection carried out by the drive controller.
No - ACL -
FCL
ACL
Choices:
No: No motor thermal protection.
ACL: Self-cooled motor. The drive controller takes into account a
derating as a function of the rotation frequency.
FCL: Force-cooled motor. The drive controller does not take into account a
derating as a function of the rotation frequency.
LossFollower LFL Allows activation of a loss of 420 mA follower
fault. This fault can only be configured if the
No No
minimum and maximum reference parameters for AI2 (CrL and CrH) are
greater than 3 mA. If CrL > CrH, LFL is automatically set to Yes.
No: Disabled
Yes: Immediate fault
STT: Stop without fault, restart on return of signal
LSF: Stop followed by fault signal from R1 and LFF display on the keypad
LFF: Run at the preset speed set by the LFF parameter
Flt. Speed 4-
20
LFF Pre-set speed in the event of the loss of the
420 mA signal.
0HSP 0
Table 21: 6Fault Menu
Parameter Code Description
Adjustment
Range
Factory
Setting
Menu
6