If the Freewheel Stop / Run Permissive function is assigned to a
logic input, the drive controller will not start the motor unless that
logic input is connected to +24 V.
Minimum Start-Up
This procedure can be used as a minimum start-up:
• In simple applications where the drive controller factory settings are
sufficient
• In installation when it is necessary to turn the motor before fully
completing the start-up sequence
Procedure:
1. Make sure that the 50/60 Hz switch is in the correct position,
corresponding to the frequency of the incoming AC power, as shown
on page 13.
2. Ensure that the macro-configuration factory setting is suitable for
the application. Refer to Table 3 on page 22. If not, change the
configuration MACRO-CONFIG menu as shown on page 21.
3. Verify that the control scheme is compatible with the macro-
configuration, ensuring that the necessary safety precautions have
been taken.
4. Verify in the 3—DRIVE menu that the factory settings are compatible
with the motor nameplate values. Refer to Table 11 on page 39.
Modify them to match the nameplate values.
5. If necessary, adjust the parameters in the 2—ADJUST menu
(ramps, motor thermal protection, etc.). See Table 6 on page 28.
If the Freewheel Stop/Run Permissive function is assigned to a logic
input, the drive controller will not start that motor unless the logic
input is connected to +24 V.