ALTIVAR
58 Keypad Display VVDED397047US R8/01
Chapter 3 Diagnostics and Troubleshooting 08/01
88
© 19982001 Schneider Electric All Rights Reserved
To measure the DC bus capacitor voltage:
1. Disconnect all power from the drive controller including external
control power that may be present on the control board and the option
board terminals.
2. Wait three minutes for the DC bus capacitors to discharge.
3. Read the model number of the drive controller from the nameplate
and identify the corresponding (+) and () measurement points from
Table 24 and Figure 25.
4. Open the door or cover of the drive controller.
5. Set the voltmeter to the 1000 Vdc scale. Measure the voltage
between the (+) and () measurement points identified in step 3.
Verify that the DC bus voltage has discharged below 45 V before
servicing the drive controller.
6. If the DC bus capacitors will not discharge below 45 V, contact your
local Square D representative. Do not operate the drive controller.
7. Replace all of the covers after servicing the drive controller.
Table 24: ATV58 Type H(+) and () Measurement Points
Drive Controller
ATV58H•••••
(+) Measurement Point () Measurement Point
Terminal
Block or
Connector
Terminal
Designation
Terminal
Block or
Connector
Terminal
Designation
U09M2 and U18M2 J2 (+) J2 ()
U29M2 to D12M2
J2 PA J18 7
U18N4 to D23N4
D16M2 to D46M2
J2 (+) J2 ()
D28N4 to D79N4