ALTIVAR
58 Keypad Display VVDED397047US R8/01
Chapter 2 Menus 08/01
52
© 19982001 Schneider Electric All Rights Reserved
FLO: Forced Local Force to local X
RST: Fault Reset Fault reset X
RFC: Auto/manu Reference switching X
ATN: Autotune Auto-tuning X
PIF: PI regulator PI regulator feedback X
[2]
X
[2]
PAV:PID Auto/Manu PID Auto/Manu if one AI = PIF X
PIM:PID Man.ref. Manual PID speed reference
if one AI = PIF
X
PR2:PID 2 Preset 2 preset PID setpoints if one
AI = PIF
X
PR4:PID 4 Preset 4 preset PID setpoints if one
AI = PIF
X
TLA:Torque limit torque limitation by AI if one
AI = ATL
X
FR2: Speed Ref2 Speed reference 2 X
SAI: Summed Ref. Reference summing X X
SFB: Tacho feedbk Tachogenerator X
PTC: Therm. Sensor PTC probes X
ATL: Torque Lim. Torque limit X
RGI: PG feedbk Encoder or sensor feedback X
Table 15: Possible Assignments for Configurable Inputs
I/O Extension Card
2 Logic
Inputs
LI5-LI6
Analog
Input
AI3
Logic
Input
[1]
A, A-,
B, B-
Drive Controller without an I/O Extension Card
Analog
Input
AI2
3 Logic
Inputs
LI2LI4
Code and
Parameter
Description
[1]
The menu for assigning encoder input A, A-, B, B- is called Assign AI3.
[2]
To configure an AI for PIF: PI regulator, RFC: Auto/manual must not be assigned to
a logic input.
Menu