Assignment of AI2 and AI3
Summing Speed Reference: The frequency setpoints given by AI2 and
AI3 can be summed with AI1.
Speed Regulation with Tachogenerator: (Assignment on AI3 only with
an I/O extension card, VW3A58201U)
An external divider bridge is required to adapt the voltage of the
tachogenerator. The maximum voltage must be between 5 and 9 V. A
precise setting is then obtained by setting the dtS parameter available in
the 2Adjust menu.
PTC Probe Processing: (only with an I/O extension card using the
analog input). Used for the direct thermal protection of the motor by
connecting the PTC probes in the motor windings to analog input AI3.
Total resistance of the probe circuit at 20 °C = 750 .
Torque Limit: (Assignment on AI3 only with an I/O extension card
VW3A58201U). This function can only be accessed if an analog input has
been assigned to the torque limit. If the logic input is at 0, the torque is
limited by setting tL1 or tL2. If the logic input is at 1, the torque is limited
by the analog input assigned to this function.
The signal applied at AI3 operates in a linear fashion on the internal
torque limit (parameter TLI in the 3Drive menu):
If AI3 = 0 V: limit = TLI x 0 = 0
If AI3 = 10 V: limit = TLI
Using the Controller Relay and Logic Outputs
The relay R2 on the drive controller or the logic output (LO) on an option
card can be configured as follows:
Output Contactor Command (OCC)
The Output Contactor Command function allows the drive controller to
command a contactor between the controller and the motor. The
controller closes the contactor when a run command is given. When there
is no longer any current in the motor, the controller opens the contactor.
When using an output contactor, set outphase loss (OPL) to No.
NOTE: If the braking by DC injection function is configured, do not exceed
contactor rating, because the contactor will not open until the end of
braking.