VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 Menus
© 19982001 Schneider Electric All Rights Reserved
37
Curr.Lev.Att- A Ctd Current threshold above which the
logic output or relay goes to state 1.
0.25 to 1.36
of I
n
[3]
1.36 of
I
n
[3]
ThermLevAtt - % ttd Motor thermal state threshold above
which the logic output or relay goes to
state 1 (high).
0 to 118% 100%
Torque lim2 -A tL2 Second torque limit, activated by a
logic input.
0% to
200%
[2]
200%
DC Inj. Curr. -A IdC DC injection braking current level.
Accessible if a logic input is assigned
to DC injection braking. After 30 s, IdC
is automatically set to 0.5 ItH if
previously set to a higher value.
0.10 to 1.36
of I
n
[3]
0.7 ItH
Accelerate 2- s
Decelerate 2- s
AC2
dE2
Second acceleration and deceleration
ramp times. These parameters are
accessible if a logic input is assigned
to ramp switching or if Frt is not 0.
0.05 to 999.9 5 s
TachFBCoeff dtS Tachometer scaling factor associated
with the tachometer feedback
function:
1 to 2 1
Table 10: 2Additional Adjustment Parameters After I/O
Reassignment (Continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
These parameters are available only with the I/O extension card installed.
Menu
2
[1]
Depending
on the position of
the 50/60 Hz
switch.
[2]
100%
corresponds to the
nominal torque of a
motor with
horsepower size
equal to that of the
drive controller at
its constant torque
rating.
[3]
I
n
= drive
controller constant
torque output
current rating
shown on the drive
controller
nameplate.
dtS
9
tachometer voltage at HSP
-----------------------------------------------------------------------
=