Chapter 3—Diagnostics and Troubleshooting VVDED397047USR6/03
Procedure 1: Bus Voltage Measurement 06/2003
98
Procedure 1: Bus Voltage Measurement
The DC bus voltage level is determined by monitoring the (+) and (–)
measurement points. Their location varies by drive controller model
number as listed in Table 26 and shown in Figure 25. The drive
controller model number is listed on its nameplate.
To measure the DC bus capacitor voltage:
1. Disconnect all power from the drive controller including external
control power that may be present on the control board and the
option board terminals.
2. Wait ten minutes for the DC bus capacitors to discharge.
DANGER
HAZARDOUS VOLTAGE
• Read and understand the bus voltage measurement procedure
before performing the procedure. Measurement of bus capacitor
voltage must be performed by qualified personnel.
• DO NOT short across DC bus capacitors or touch unshielded
components or terminal strip screw connections with voltage
present.
• Many parts in this drive controller, including printed wiring boards,
operate at line voltage. DO NOT TOUCH. Use only electrically
insulated tools.
Electrical shock will result in death or serious injury.
Table 26: ATV58 TRX Type H (+) and (–) Measurement Points
Drive Controller
ATV58H••••••
(+) Measurement Point (–) Measurement Point
Terminal
Block or
Connector
Terminal
Designation
Terminal
Block or
Connector
Terminal
Designation
U09M2• and U18M2• J2 (+) J2 (–)
U29M2• to D12M2•
J2 PA J18 7
U18N4• to D23N4•
D16M2• to D46M2•
J2 (+) J2 (–)
D28N4• to D79N4•
C10N4• to C33N4• PA (+) PC (–)