
© 1998–2003 Schneider Electric All Rights Reserved
Chapter 2—Menus VVDED397047USR6/03
5—I/O Menu 06/2003
62
After the I/O have been assigned, additional parameters related to
the functions automatically appear in the menus, and the macro-
configuration is CUS: Customized. The additional parameters are
listed in Tables 17 and 18.
OPI:PI Integral
PI integral output, if one AI is
assigned to PIF
X
OPR:Motor power Motor power X
THR: Motor Thermal Motor thermal state X
THD: Drive Thermal Drive thermal state X
Table 16: Possible Assignments for Configurable Outputs
I/O Extension Card
Analog
Output
AO
Logic
Output
LO
Drive Controller without an I/O Extension Card
Relay
R2
Analog
Output
AO1
[1]
These parameters are not available on 125–500 hp drive controllers.
Menu
5
Table 17: New Parameters in 2—Adjust Menu After I/O
Reassignment
I/O Assignment New Parameters to Adjust
LI RP2 Ramp switching AC2 dE2
LI JOG Jog JOG JGt
LI PS4 4 preset speeds SP2 SP3
LI PS8 8 preset speeds SP4 SP5 SP6 SP7
LI DCI DC injection braking IdC
LI TL2 Second torque limit
[1]
tL2
LI PR4 4 preset PI setpoints P12-P13
AI PIF PI regulator rPG rIG FbS PIC
AI SFB Tachogenerator dtS
R2 BLC Brake logic
[1]
brL Ibr brt bEn
bEt
R2, LO FTA Frequency threshold attained Ftd
R2, LO CTA Current threshold attained Ctd
R2, LO TSA Motor thermal threshold attained ttd
[1]
These parameters are not available on 125–500 hp drive controllers.
Menu
2
Comentarios a estos manuales