Chapter 2—Menus VVDED397047USR6/03
Macro-Configuration Menu 06/2003
24
Table 3: Drive Controller I/O Assignments
Hdg: Material
Handling
[1]
GEn: General
Use
VT: Variable
Torque
NOTE: LI1, AI1,
and R1
assignments are
not visible in the
5—I/O menu. LI1
and R1 cannot be
reassigned.
Logic Input LI1 Forward Forward Forward
Logic Input LI2 Reverse Reverse Reverse
Logic Input LI3 2 Preset speeds Jog Auto/manual
[3]
Logic Input LI4 4 Preset speeds Freewheel stop
[2]
DC injection
braking
[3]
Analog Input AI1 Reference summing Reference summing Speed reference 1
[3]
Analog Input AI2 Reference summing Reference summing Speed reference 2
[3]
Analog Output AO1 Motor frequency Motor frequency Motor frequency
Relay R1 Drive fault relay Drive fault relay Drive fault relay
Relay R2
Output contactor
control
Motor thermal level
attained
Frequency reference
attained
[3]
[1]
Factory default setting for 100 hp products and below.
[2]
If the Freewheel Stop/Run Permissive function is configured, the drive controller will
not start the motor unless the logic input is connected to +24 V.
[3]
For 125–500 hp drive controllers the factory setting are:
LI3 = Fault Reset; LI4 = Not assigned; AI1 = Reference summing; AI2 = Reference
summing; R2 = Drive running
Table 4: I/O Extension Card Factory Presets
Hdg: Material
Handling
[1]
GEn: General
Use
VT: Variable
Torque
NOTE: You must
ensure that the
functions which
are programmed
are compatible
with the control
scheme used.
Logic Input LI5 8 preset speeds Fault reset Freewheel stop
[1]
Logic Input LI6 Fault reset Torque limit 2
[3]
Ramp switching
Analog Input AI3
[2]
or Logic Inputs A, A-,
B, B-
[3]
Reference summing
[2]
Reference
summing
[2]
Not assigned
[2]
Speed feedback Speed feedback Speed feedback
Logic Output LO
Current level
attained
Output contactor
command
High speed attained
Analog Output AO Motor current Motor current Motor current
[1]
If the Freewheel Stop / Run Permissive function is configured, the drive controller will
not start the motor unless the logic input is connected to +24 V.
[2]
With analog I/O extension card (VW3A58201U).
[3]
With digital I/O extension card (VW3A58202U).