VVDED397047USR6/03 Chapter 2—Menus
06/2003 2—Adjust Menu
29
2—Adjust Menu
The Adjust menu is accessible when the access locking switch is set
to either partial lock, , or total unlock, . Adjustment
parameters can be modified with the motor running; however, you
must make all adjustments with the motor stopped to avoid
unintended equipment action.
Run time rtH Operating time (motor powered up) in hours hrs
Freq. Ref LFr
This adjustment parameter appears in place of
the FrH parameter when command of the drive
controller by the keypad display has been
activated with the LCC parameter in the
4—Control menu (see page 56).
Hz
LCU LCU
Local speed control in customer-defined units.
User
depen-
dant
Appears when the drive controller command from the
keypad display has been activated using the LCC
parameter in the 4—Control menu (see page 56). This
parameter allows adjustment of the motor speed in
customer-defined units. Use parameter USC: Machine
Coef. to scale the customer unit value (see page 34).
During adjustment, LCUA appears in the lower left-hand
corner of the keypad display.
Table 5: 1—Display Menu Parameters (continued)
Parameter Code Function Units
Menu
1
WARNING
PARAMETER CHANGES WHILE THE MOTOR IS RUNNING
Changes made to adjustment parameters while the motor is
running may cause unintended equipment action. When changing
adjustment parameters, ensure that the motor is stopped.
Failure to follow this instruction can result in death, serious
injury, or equipment damage.