VVDED397047USR6/03 Chapter 2—Menus
06/2003 4—Control Menu
53
Table 13: 4—Control Menu: 2-Wire Control Type
Parameter Code Description
Adjustment
Range
Factory
Setting
NOTE: Type 2
Wire appears only
if 2-wire control is
selected.
Type 2 Wire tCt
Defines the type of 2-wire
control:
LEL-TrN-
PFW
LEL
• LEL: If the forward or reverse input is high when the
drive controller is powered up, the drive controller will
start the motor. If both inputs are high on power up, the
controller will run forward.
• TrN: The drive controller must see a transition from low
to high of the forward or reverse input before it will start
the motor. Therefore, if the forward or reverse input is
high when the drive controller is powered up, the input
must be cycled before the drive controller will start the
motor.
• PFW: Forward input has priority over reverse input with
this control. If forward is activated while the controller is
running in reverse, the controller will run forward.
2-wire control wiring example:
RV inhibit rln
When configured for Yes, this
function inhibits reverse
operation even if reverse
operation is requested by a
summing or PI regulator
function.
Yes - No No
This parameter is not available if a logic input is configured
for reverse. A logic input cannot be configured for reverse if
this parameter is configured for Yes.
★ These I/O can be accessed if an I/O extension card has been installed.
[1]
For 125–500 hp drive controllers the factory setting are:
LI4 = Fault Reset; LI5 = ramp switching; LI6 = Not assigned
Menu
4
ATV58 TRX terminal strip
24 V LI1
LIx
LI1: Forward
LIx: Reverse