VVDED397047USR6/03 Chapter 2—Menus
06/2003 2—Adjust Menu
39
Additional Adjustment Parameters After I/O Reassignment
Table 10 lists the additional parameters that may be accessible after
the inputs or outputs have been reassigned.
Table 10: 2—Additional Adjustment Parameters After I/O
Reassignment
Parameter Code Description
Adjustment
Range
Factory
Setting
Preset Sp.2-Hz SP2 Second preset speed LSP to HSP 10 Hz
Preset Sp.3-Hz SP3 Third preset speed LSP to HSP 15 Hz
Preset Sp.4-Hz SP4 Fourth preset speed LSP to HSP 20 Hz
Preset Sp.5-Hz SP5 Fifth preset speed LSP to HSP 25 Hz
Preset Sp.6-Hz SP6 Sixth preset speed LSP to HSP 30 Hz
Preset Sp.7-Hz SP7 Seventh preset speed LSP to HSP 35 Hz
Jog Freq. - Hz JOG Frequency when operating in jog 0 to 10 Hz 10 Hz
Jog Delay - s JGt
Delay between two consecutive
jog operations.
0 to 2 s 0.5 s
BrReleaseLev-Hz
[4]
brL Brake release frequency 0 to 10 Hz 0 Hz
BrReleaseI -A
[4]
Ibr Brake release current
0 to 1.36 of
I
n
[3]
0 A
[1]
Depending on the position of the 50/60 Hz switch.
[2]
100% corresponds to the nominal torque of a motor with horsepower size equal to that
of the drive controller at its constant torque rating.
[3]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[4]
This parameter is not available on 125–500 hp drive controllers.
These parameters are available only with the I/O extension card installed.