VVDED397047USR6/03 Chapter 2—Menus
06/2003 5—I/O Menu
67
and the -Speed input decreases the speed. If logic inputs are
assigned to +Speed/-Speed, the Str parameter appears in the
4—Control menu allowing the reference speed to be saved (see
page 56).
NOTE: When 3-wire control is selected, -Speed is automatically
assigned to the next input after the one assigned to +Speed.
2. Use of selector switches. Only one logic input, assigned to
+Speed, is required. When using selector switches, there is one
position for each rotation direction.
NOTE: This type of operation is not compatible with 3-wire
control.
The Save Reference (Str) parameter can be used to save the last
speed reference when the run command is removed or when the
power is removed.
In both types of operations, the maximum speed is set by the
reference speeds at the analog inputs. For example, if 60 Hz is the
desired maximum speed, a jumper can be installed from +10 Vdc to
AI1.
Figures 13 and 14 illustrate wiring and timing for +Speed/-Speed.
Figure 13: +Speed / -Speed Wiring Diagram
a b A B
LI1 LI2 LI3 LI4 +24 AIX
Activate input a or b,
then activate input A or B.
LI1: Forward
LI2: Reverse
LI3: +Speed
LI4: –Speed
ATV 58 TRX terminal