VVDED397047USR6/03 Chapter 3—Diagnostics and Troubleshooting
06/2003 Fault Codes and Messages
105
Ini
Attempting to download an
incompatible file from the keypad
display to the drive controller.
Incompatibility can be caused by
transferring to a drive controller with
dissimilar part numbers. Also,
incompatibility can occur when files are
created on a drive controller with new
firmware and then attached to a
controller with older firmware. The
error may appear after ERR7 is
displayed.
1. Ensure that the file being downloaded
was created for the correct drive
controller part.
2. Verify drive controller firmware.
Reconfigure the new features used in
the newer firmware. Like
configurations are transferable
independent of firmware revision.
Another option is to upgrade the
firmware by ordering part number
VX4A581U.
Cycle power on the drive controller.
LFF
LOSS OF 4-20 mA
Loss of 4–20 mA follower signal on AI2
input. See Table 29 on page 107.
1. Verify signal connections.
2. Check signal.
ObF
OVERBRAKING
Overvoltage or overcurrent due to
excessive braking or an overhauling
load. See Table 28 on page 106.
Increase deceleration time. Add a
dynamic braking option if necessary, or
verify that the dynamic braking option is
working properly.
OCF
OVERCURRENT
Ramp too short.
Inertia too high, or load too large
Mechanical blockage.
1. Check the parameter settings.
2. Check the sizing of the drive controller,
motor, and load.
3. Remove all power. With the drive
controller disconnected, check for
mechanical blockage.
OHF
DRIVE OVERHEATING
Heatsink temperature too high.
Check the motor load, fan, and the
ambient temperature around the drive
controller. Wait for the drive controller to
cool down before resetting.
OLF
MOTOR OVERLOAD
If the thermal trip setting meets or
exceeds 118% of the normal
thermal state, thermal trip is due to
prolonged overload or output
phase failure.
Motor power rating is too low for
the application.
Check the setting of Thermal Current
(
ItH, see page 32) and compare it
with motor I
n
(nameplate current
rating). Check the load and compare it
with operating speed. Check the
braking conditions (possibility of
single-phase operation). Wait
approximately seven minutes before
resetting.
Verify that the motor and drive
controller selections are correct for
application.
OPF
MOTOR PHASE LOSS
Loss of a phase on the output of
the drive controller.
Drive controller oversized for
motor.
1. Check the wiring to the motor
(Procedure 3 on page 102).
2. Disable OPL and provide external
overload protection.
OSF
OVERVOLTAGE
Supply too high. See Table 28.
1. Check the input line voltage
(Procedure 2 on page 101).
2. Reset the drive controller.
Table 27: Fault Codes and Messages (continued)
Fault/Message Probable Causes Corrective Actions