Vista de pagina 26
© 1998–2003 Schneider Electric All Rights Reserved
VVDED397047USR6/03 Chapter 2—Menus
06/2003 Drive Controller Identification Screen
27
Increasing the Power Rating for Variable Torque Applications
The power rating can be increased for variable torque applications on
the drive controller identification screen for the following products:
208/230 Vac drive controllers 15 hp and larger
(ATV58HD16M2–D46M2)
400/460 Vac drive controllers 25 hp and larger
(ATV58HD28N4–D79N4)
460 Vac drive controllers 5 hp to 25 hp that do not have an
integrated EMC filter (ATV58HU54N4X–D23N4X)
To increase the horsepower rating, begin at the rEF screen and
follow this procedure:
1. Press ENT. rEF begins flashing.
2. Press . A higher horsepower rating is displayed with a “+” sign
indicating that the rating has been increased.
3. Press ENT then ESC. The drive controller is now configured for
the higher horsepower rating.
Figure 11: Drive Controller Identification Screen