Chapter 2—Menus VVDED397047USR6/03
6—Fault Menu 06/2003
86
Nb max reset nAr
This parameter is used to set the
number of restart attempts.
0-255 5
Reset pause tAr
This parameter sets the delay
time between Auto restart
attempts.
0.1 to 999.9 s 30.0 s
NOTE: Reset
Type is accessible
if the Reset Fault
function is
assigned to a logic
input.
Reset Type rSt
Faults reset by a partial reset
(rSt = RSP) are:
OSF Input line overvoltage
ObF overbraking
OtF motor overheating
LFF loss of 4–20 mA
OLF motor overload
RnF ramp not followed
SOF overspeed
OPF motor phase loss
OHF drive overheating
SLF loss of RS-485 port
communication
EPF external fault
CnF network communication
fault
RSP
(partial reset)
RSG
(total reset)
RSP
All faults except motor short circuit are reset by a total reset
(rSt = RSG).
Total reset overrides all other faults. To configure rSt to
RSG:
1. Display RSG
2. Press the ENT key.
3. The drive controller displays “See manual”.
4. Press the up arrow key, then the down arrow key, then
ENT twice.
Table 21: 6—Fault Menu
Parameter Code Description
Adjustment
Range
Factory
Setting
This parameter is only available on 125–500 hp drive controllers.
Menu
6
CAUTION
MOTOR OVERHEATING
Repeated reset of the thermal state after a thermal overload can result in thermal
stress to the motor.
When faults occur, promptly inspect the motor and driven equipment for problems
such as locked shaft and mechanical overload before restarting. Also check the
power supplied to the motor for abnormal conditions such as phase loss and phase
imbalance.
Failure to follow these instructions can result in equipment damage.