Chapter 2—Menus VVDED397047USR6/03
7—Files Menu 06/2003
92
If storing a file, the display automatically returns to the FOt
(Operation Type) parameter after storing the file.
If the FOt parameter is set to REC, a second confirmation must be
made:
The display indicates:
Press ENT to confirm.
The display then indicates:
Press ENT to confirm.
The display automatically returns to the FOt parameter, set to No.
Access Code
The drive controller configuration can be protected by an access code
(password).
NOTE: Use this parameter with caution. It can prohibit access to
parameters. Carefully note and save any modification to this
parameter.
The access code is expressed with four digits. The first three are
user-assigned and do not affect access to the menus. The fourth digit
can range from 0 to 9 and determines which menus can be accessed.
See Table 24 for an explanation of the last digit codes.
For example, if the access code is “2337”, display of the menus 2, 3,
4, 5, 6, 7, and 8 is allowed, but modification is not allowed.
Validate? ENT/ESC
CHG
Wiring OK? ENT/ESC
CHG
Table 23: Access Code
Parameter Code Description
Factory
setting
Config. Code
COd
Configuration code used as an access
code.
0000
Figure 22: Access Code
8888
this number gives the
authorized level of access