Specifications
A–2 975-0540-01-01 Revision B
This guide is for use by qualified personnel only.
Electrical Specifications
Maximum PV Array Open Circuit Voltage 600 VDC
PV Array Voltage Operating Range 195 to 550 VDC
PV Array Voltage Full Power Range
a
a.Full power output below 230 V is not assured. See “Operating Below the PV Array Voltage Full Power Range” on
page A–3 for more information.
230 to 550 VDC
Maximum Power Point Tracking Range 195 to 510 VDC
PV Input Start Voltage 230 VDC
Maximum Operating Current 23 A
Maximum Array Short Circuit Current at STC 28 A
Absolute Maximum Array Short Circuit Current
Under Any Conditions
35 A
(See the Notice on the next page for more
information)
Nominal Battery Voltages 24 and 48 VDC (Default is 48 V)
Battery Voltage Operating Range 16 to 67 VDC
Maximum Charging Current 80 A
Maximum Charging Power 2560 W (nominal 24 V battery bank)
4800 W (nominal 48 V battery bank)
Maximum Power Conversion Efficiency 94% (nominal 24 V battery bank)
96% (nominal 48 V battery bank)
Auxiliary Output Dry contact switching up to 60 VDC, 30 VAC, 8 A
Charger Regulation Method Three stage (bulk, absorption, float)
Two stage (bulk, absorption)
Manual equalization
Tare Losses
b
b.These values are based on the following specifications:
- The battery voltage is 48 V.
- The auxiliary power supply is shut off at night. See “Disabling Power Supplies at Night” in the Xantrex XW MPPT 80 600
Solar Charge Controller Operation Guide for more information.
less than 1.0 W (Xanbus power supply on)
less than 0.5 W (Xanbus power supply off)