Installation
2–4 975-0540-01-01 Revision B
This guide is for use by qualified personnel only.
To help ensure optimal and safe operation, make sure there is adequate
clearance around the charge controller. See Table 2-1 and Figure 2-1. If
clearances are reduced below these minimums, charging performance might be
impaired.
Table 2-1 Minimum clearance requirements
Location Minimum Clearance
Above
and below
6 inches (150 mm). Do not mount charge controllers in a vertical
stack.
One charge controller can be mounted on the side of the Xantrex
XW Power Distribution Panel (PDP
)
a
(
part number 865-1015
). For
more information,
see the Xantrex XW Power System Installation
Guide, available with the Xantrex XW Hybrid Inverter/Charger.
Other installations must follow the guidelines in this Guide.
a.The PDP is not available outside North America.
In front Sufficient room to allow for easy access to see the LEDs and to
perform maintenance.
Sides No clearance requirement.
Figure 2-1 Minimum clearance requirements
6 inches (150 mm) above
6 inches (150 mm) below