Mounting
975-0540-01-01 Revision B 2–3
This guide is for use by qualified personnel only.
Mounting
The instructions in this chapter are applicable to a typical stand-alone
installation. Installation procedures will vary according to your specific
application. For special applications, consult a qualified Renewable Energy
System Installer or a Certified Dealer.
Choosing a Location
WARNING
HAZARD OF ELECTRIC SHOCK AND FIRE
The PV array voltage must never exceed 600 V
OC
, including the local
temperature correction factor required by the local electrical code. The PV
array maximum circuit current must not exceed 35 A, including the multiplier
required by the local electrical code. For example, the multiplier required by
the NEC and the CEC is 125%, so the array STC I
sc
must not exceed 28 A
(28 A x 125% = 35 A).
Failure to follow these instructions can result in death or serious injury.
WARNING
HAZARD OF ELECTRIC SHOCK, BURN, FIRE, AND EXPLOSION
RISK OF EQUIPMENT DAMAGE
The charge controller must be mounted vertically and installed indoors in a
dry, protected location away from flammable materials, sources of high
temperature, moisture, and vibration. The location must also be sheltered from
direct sunlight, dust, and wind-blown debris.
Failure to follow these instructions can result in death or serious injury.
WARNING
HAZARD OF EXPLOSION
Do not install the charge controller in a sealed compartment containing
batteries.
Failure to follow these instructions can result in death or serious injury.