Installation Instruction 66571764GB3 Fire Detection 43
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
18.3 Modem connections in the communication network
FxNet
1 2
SYSTEM SYSTEM
SAB
FxNet
1 2
SYSTEM SYSTEM
SAB
FxNet
1 2
SYSTEM SYSTEM
SAB
1 2 .... N
FxNet
1 2
SYSTEM SYSTEM
SAB
FxNet
1 2
SYSTEM SYSTEM
SAB
FxNet
1 2
SYSTEM SYSTEM
SAB
FxNet
1 2
SYSTEM SYSTEM
SAB
FxNet
1 2
SYSTEM SYSTEM
SAB
FxNet
1 2
SYSTEM SYSTEM
SAB
5 6 .... X 22 23 .... 32
CodiNet
rs232<=>485
converter
CodiNet
rs232<=>485
converte
r
Fiber
Modem
Fiber
Modem
Tx Rx
Fiber
Modem
Fiber
Modem
Tx Rx
Fiber
Modem
Fiber
Modem
Tx Rx
Tx Rx Tx Rx Tx Rx
2x 2W Rs 485 (system1 and system2)
Max cable length 1000m
Rs 485 / fibre modems ( Moxa)
Multi- or single mode fibres
max.fibre legth is depending of the fibre type
Fiber
Modem
Fiber
Modem
Group of
Fx-panels
Fiber
Modem
Fiber
Modem
Group of
Fx-panels
NOTE!
Do NOT connect panels so that the signal path
between any panels goes thru more than
two modem pairs / line
No modem
connections on
this point !
Panels can be connected
to this point with modems
Fiber
Modem
Fiber
Modem
Tx Rx Tx Rx
CodiNet
rs232<=>485
converter
CodiNet
rs232<=>485
converter
CodiNet
rs232< =>485
converter
CodiNet
rs232<=>485
converter
CodiNet
rs232<=>485
converter
CodiNet
rs232<=>485
converter
rs-232
rs-232
rs-232
rs-232
rs-485
rs-485
rs-485
rs-485
NOTE 2!
Even if the fiber modem have rs-485 connections
it’s allways recommended to use it on rs-232 mode and
use CodiNet- coverter between the fiber modem and
the panel if the lentgh of the copper cable on the
rs-485 connection is more than ~100m
Picture 7. Max. two modem pairs between two panels
1. Disconnect all power from the control panel.
2. Connect the RS485 serial communication wires to
the
RS485 terminals (INFO) and
System1 terminals (RS485 type) and
System2 terminals (RS485 type) as follows
Signal wires to terminals T/R + and T/R and GND.
(Note that shield wire of the cable can not be
connected to the GND terminal).
The shields of the cables may not be connected to
the metal part (earth) of the cabinet directly. The
shields must be connecter through the parallel
connected capacitor and varistor as follows
(because long distances may cause big differences
in earth potential). Loosen three screws of the
backplate. Install the small circuit board from the SA
package under the screws and tighten the screws
and connect the shield to the terminals.
3. Connect the RS232 serial communication
conductors to the RS232 terminals as follows:
The control panel transmitter wire to terminal TxD
The control panel receiver wire to terminal RxD.
GND wire (not shield) to terminal GND.
Connect the shield directly to the metal part (earth)
of the cabinet.
4. Start the control panels: first visible panels and
then seeing panels
5. If the control panel gives an earth leak indication, line fault (one of S1 and S2 is not functioning) or
communication fault (either of S1 and S2 is not functioning), press the “BUZZER SILENCE”- button and
disconnect all power from the control panel. Repair any fault and restart the control panel.
6. If the control panel has been configured, the operation of serial communication should be tested
(remember that a fire or fault also activates fire or fault alarm devices and alarm routing equipment).