Installation Instruction 66571764GB3 Fire Detection 32
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
13. Monitored output lines
13.1 Measuring the cables and connecting the end-of-line resistors
1. Disconnect all power from the control panel.
2. Measure the resistance between the monitored output line
cable wires so that the resistance meter positive (feeding)
measuring end is in the ““ wire of the line. The resistance
meter must indicate a break. If the resistance meter
indicates a resistance value, the cause of the fault must
be located. (It may be an alarm device connected the
wrong way, a serial diode missing from the alarm device
or a short circuit in the conductors).
Loop 2
A+ A-
Loop 2
B+ B-
Loop 1
A+ A-
Loop 1
B+ B-
PO 2
+24V-
PO 1
+24V-
OL
3. Short-circuit the monitored output line cable wires at the
control panel during measuring.
4. Disconnect the end-of-line resistors from those monitored
output line outputs to which the cables are to be
connected.
5. Measure the resistance between the wires of the cable at
the last alarm device or end-of-line unit box in each
monitored output line with the resistance meter. The
allowed resistance should not be more than 300
depending on the current consumption of the alarm
devices connected to the same line (See picture on the
right). If the resistance is considerably higher, there is a
break in the line (did you remember short-circuit the cable
wires at the control panel). Locate the breaks and
eliminate them.
6. Take the end-of-line resistors to their respective places
(the last alarm device of the line or the end-of-line unit box
connected after the last alarm device) and connect them.
Note!
There must not be other resistors or end-of-line units in the
monitored output line.
<300Ω
4k7