Installation Instruction 66571764GB3 Fire Detection 34
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
14. Control outputs
14.1 Clean relay outputs
The FX-MC2 board has three clean contact outputs.
Each FX-IOC board has two clean contact outputs.
Each FX-OCA board has 16 clean contact outputs.
The function of the outputs is defined with the configuration tool.
The default functions of the outputs of a control panel that has not been configured are:
Fire alarm router activation
Note! If the ‘Side CPU not in use’- jumper is in place in the
MC2 (system assistant processor is NOT in use), then in
the case of the MC2 system fault the system assistant
processor does NOT control the CO1 output as a fire
router output regardless of the configuration.
Fault warning router activation
The relay is energized in normal condition and releases in
fault warning condition or if power is removed regardless of
the configuration.
Maintenance warning output
1. Disconnect all power from the control panel.
2. Select suitable outputs and connect the device to be controlled
to the output.
The relay contacts are rated for max. 30 VDC, 1 A.
WARNING!
Voltage 230 VAC must not be brought to the relay contacts.
If a device with 230 VAC is to be controlled, a suitable intermediate
relay must be used. It is to be placed in a casing outside the
control panel cabinet and equipped with a protective diode (e.g.
CO3
NO C NC
CO2
NC C NO
CO1
NO C NC
RS232
Tx Rx Gnd
CO1
NO C NC
SYS 1
Gnd - +
SYS 2
Gnd - +
Test the fire outputs control operation as follows:
1. Start the control panel.
2. Press the wheel to activate the menu and select:
3. Then press again the wheel and select:
4. Press the “TEST”- button, at which the display will show the
text:
PRESS WHEEL TO ACTIVATE THE
CONTROL
5. Pressing the wheel activates all control outputs.
6. The test is stopped by pressing the “TEST”- button.