12.3 Connecting the line to the control panel
Each CLC board has 16 conventional lines (detection circuits).
1. Disconnect all power from the control panel.
2. If shielded cable is used, connect the shield to the cabinet ground
screw in the back plate.
Note!
The free shielded wire must be as short as possible!
3. Connect the pair of wires of the conventional line to the terminals
of the CLC board retaining polarity.
+ 2 -+ 5 -
+ 7 -
+ 6 -
+ 8 -
+ 9 -+ 10 -
+ 12 -
+ 13 -
+ 15 -
+ 14 -
+ 16 -
+ 1 -
+ 4 -
+ 3 -+ 11 -
12.4 Functional check of the loop
1. Start the control panel by switching the power on.
First connect the transformer cable, then
the battery cable.
2. Wait until the text “PANEL STARTING UP” disappears
from the display (about 3 minutes).
The detector loop is in order if the control panel does not give fire, fault or service indications at the start up.
Otherwise the fault must be located by following the instructions below.
3. If the panel indicates fire alarm, press the “BUZZER
SILENCE” button, scroll the alarm indications with the
“MORE ALARMS”- button and note them.
4. Eliminate the causes of fire alarm and reset the indications
by pressing the “RESET”- button until the pulsed signal
stops.
5. Repeat the above mentioned procedures until there are no
Possible causes for fire alarm:
- A manual call point is pressed down; the
glass has been broken or taken off.
- Smoke, water vapour or thick dust in a
smoke detector.
- Heat close to a heat detector.
6. If the panel indicates fault or maintenance warning press
the “BUZZER SILENCE” button, scroll the indications with
the “MORE ALARMS”- button and note them.
7. Eliminate the causes of fault and maintenance warnings
and reset the indications by pressing the “RESET”- button
until the pulsed signal stops.
8. Repeat the above mentioned procedures until there are no
more fault and maintenance warnings.
Possible causes for fault warnings:
- A break or a short circuit in the loop.
- An earth leak in the loop.
Note!
CLC default value for the short circuit is a
fault!
9. Test that each detector and manual call point gives an
alarm. Test procedures for the various devices are given in
the documentation for those devices.