SLC jumper settings
1. Check the following settings:
“Prog Update” jumper is not in place.
“Dev LED” jumper is in place if you want the detector
leds to flash when communicating with the panel or
not in place otherwise.
Set the right ID. The range is 1…4/panel and is
common to SLC, ALC and CLC units.
2. Check also that there is a wire between A+ and B+
as well as between A- and B- in the terminals for both
loops.
CLC jumper settings
1. Check the following settings:
Set the right ID. The range is 1…4/panel and is common to
SLC ALC and CLC units.
Check also that all conventional line terminals have their
EOL resistors connected to the terminals.
ALC jumper settings
1. Check the following settings:
“Prog Update” jumper is not in place.
“Dev LED” jumper is in place if you want the detector leds to
flash when communicating with the panel or not in place
otherwise.
Set the right ID. The range is 1…4/panel and is common to
SLC, ALC and CLC units.
2. Check also that there is a wire between A+ and B+ as well
as between A- and B- in the terminals for both loops.
IOC jumper settings
1. Check the following settings:
Set the right ID. The range is 1…4/FX and FXL panel. The
ID must be different for each IOC and OCA.
The monitored output line configuration jumpers are set for
desired operation (pulsed or continuous signal).
Check also that there are 4.7kΩ end-of-line resistors in the
terminals for each monitored output line.