Installation Instruction 66571764GB3 Fire Detection 33
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
13.2 Connecting the monitored output lines to the control panel
The FX-MC board has one monitored output line connector.
Note!
If the ‘Side CPU not in use- jumper is NOT in place in the MC2 (system assistant processor is in use),
then in the case of the MC2 system fault the system assistant processor controls the CO1 output as a
fire router output regardless of the configuration.
The FX-IOC board has four monitored output line connectors.
1. Check that all power has been disconnected from the
control panel.
2. Connect the monitored output line cable wires to the
terminals as follows:
- The fire alarm line is connected to the output marked
with bell symbol on the MC and the outputs 1 to 3
marked with the bell symbol on the IOC.
- The fault alarm line is connected to the output 4
marked with the bell symbol on the IOC.
- 4.7 k resistors are left in the terminals of outputs that
are not in use.
Note!
The above usages of the outputs are valid for non-configured
panels. If configured, the purpose may have been changed.
Verify with the configuration.
+ 4 - + 3 - + 2 - + 1 -
4k7
4k7
4k7
4k7
13.3 Functional check of monitored output lines
1. Start the control panel. The monitored output lines are in
order if the control panel does not give fault indications.
2. If the alarm devices give fault indications, press the
BUZZER SILENCE”- button on the user panel.
3. You may also want to silence fault warning devices by
pressing the “SILENCE/RESOUND” button.
Possible causes of fault indications:
- A short circuit in the line, the end-of-
line resistor is too small (should be
4.7k), a serial diode is missing from
an alarm device or the device has
been connected with the wrong
polarity.
- A break in the line, the end-of-line
resistor is missing or its resistance is
too big.
- An earth leak in the line.
4. Eliminate the causes for fault indication and reset the panel
by pressing the “RESET”- button until the audible signal
stops.
5. Test the monitored output line operation as follows:
Note! Ensure that all persons in the
building have been informed of the alarm
device test.
6. Press the wheel to activate the menu and select:
CONTROLS
7. Then press the wheel again and select:
FIRE ALARM DEVICES CONTROL
8. Press the “TEST- button, at which the display will show the
text:
PRESS WHEEL TO ACTIVATE THE
CONTROL
Pressing the wheel activates all fire alarm devices.
9. The test is stopped by pressing the “TEST”- button. Check
the operation of the alarm devices. Eliminate any faults and
repeat the test until all alarm devices operate.