Installation Instruction 66571764GB3 Fire Detection 17
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
OCA jumper settings
1. Check the following settings:
Set the right ID. The range is 1…4/FX and FXL panel. The
ID must be different for each IOC and OCA.
9. Control panel test run: Note differences with the FXS!
9.1 Mains connection
Note! The panel is in access level 2 when the cover is removed.
1. Switch the panel on by connecting the cable between
the transformer and the terminal 30VAC on the power
supply component board.
FXS: Connect power supply cables “P1” and “P2” to the
MC2 PI1 and PI2 terminals.
The backlight of the display flashes for about 20 s.
The display will show the text:
The text “Panel starting up” will disappear from the display
when all addresses are scanned for presence.
FX
Fire Panel
Activate menu by pressing wheel
After approximately one minute from start the panel will
indicate a fault alarm due to the missing battery:
Note: FXS does not give any fault alarm, because there in
FXS is not built-in power supply and battery.
Buzzer beeps continuously.
FAULT-led blinks.
LCD display shows:
PS battery fault
2. Press the “BUZZER SILENCE”- button.
The audible signal is silenced.
The “FAULT”- led becomes fixed.
The LCD remains the same.
The panel will also indicate a fault alarm for missing.
configuration data if the panel is not configured.
This fault alarm can be reset and will not appear again.