Installation Instruction 66571764GB3 Fire Detection 42
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
18.1 FX 3NET communication network
S1
S1
S1 S1 S1
S2
S2
S2
FX_ FX_
FX_ FX_
FX_ FX_
FX_
“Visible” “Visible”
“Visible” “Visible”
“Seeing” “Seeing”
“Seeing”
Fire Routing
Building 1
= Communication cable
- one twisted pair
- shielded
Building 2
FRE
S2 S2
S1
System 1(S1) and System 2 (S2) = serial communication line
Picture 5. Example: FX 3NET communication network
18.2 Communication grounding
FX y serial adapterFX x serial adapter
GND TR- TR+
SYSTEM 2
SYSTEM 1
GND TR- TR+
2b, Spare wire,
not in use
2b, Spare wire,
not in use
1a
1b
2a
1a
1b
2a
TR+ TR- GND
SYSTEM 1
SYSTEM 2
TR+ TR- GND
1a
1b
2a
1a
1b
2a
2b, Spare wire,
not in use
2b, Spare
wire, not in use
TR+ TR- GND
RS485
FMPX
GND TR- TR+
RS485
2b, Spare wire,
not in use
2b, Spare wire,
not in use
2a
1b
1a
2a
1b
1a
FX y
chassis
FX x
chassis
All serial
communication
cable shields are
connected to the
grounding filter.
Max length 10mm
Cable shield is
connected ONLY
in FXNET panel
All serial
communication cable
shields are connected
to the grounding filter.
Max length 10mm
Picture 6. Communication grounding in the FX NET system