System Components and Accessories
975-0239-01-01 1–5
This manual for use by qualified personnel only
Figure 1-4 Power Distribution Panel and Xantrex XW Conduit Box
Xantrex XW Power Distribution Panel includes:
Power Distribution Panel enclosure with a field-reversible panel door
Mounting Plate
Xantrex XW Conduit Box
Xantrex XW Power Distribution Panel
Mounting Plate
Xantrex XW Conduit Box
The panel door can be mounted on the right or left side of the Xantrex XW
Power Distribution Panel.
AC Knockout slots = 9 (for dual 60A Square D, type QOU breakers)*
DC Knockout slots = 8 small (for 60A DC breakers) and 3 large
(for GJ breakers)
*AC Breakers cannot exceed 60A.
The enclosure comes pre-wired with:
3x 60A, 120/240 Vac, 2-pole, Square-D, Type QOU, DIN-rail
mounted AC breakers (pre-wired to connect to one Xantrex XW
inverter)
1x GJ250A 160 Vdc, 3/8" stud DC breaker
2x Ground terminal bus bars
1x Neutral terminal bus bar
1x Negative bus bar
1 pair #4/0 AWG Battery Cables
Xantrex XW PDP Dimensions:
30" (761mm) H x 16" (406mm) W x 8 ¼" (210mm) D
Depth from the wall = 8 ¾" (223 mm)