Xantrex XW System Accessories Installation
5–18 975-0239-01-01
This manual for use by qualified personnel only
Connecting an External ON/OFF LED
Wires 9 (White/Blue) and 11 (Black) on the wiring harness can be connected to
an LED or other light to accompany a remote external O
N/OFF switch. This light
turns on when the generator run signal is active to visually indicate that the
generator is running.
Important: With some generators, the generator run signal becomes active
during the preheat stage, before the generator is actually running. In this case,
the external O
N/OFF LED (and the Generator On light on the Xantrex XW
Automatic Generator Start) will turn on during the preheat stage and remain on
when the generator is running.
For some generators, these lights will also remain on for a period of time after the
generator has stopped.
Figure 5-10 External ON/OFF Switch and LED Wiring Diagram
START PUSH BUTTON
STOP PUSH BUTTON
12V OR 24V
EXTERNAL LED
EXTERNAL LED
GROUND
7
8
9
10
11
13
2K
2K
5K11
Xantrex XW Automatic Generator Start
Vista de pagina 131