Schneider Electric Xantrex XW Guía de instalación Pagina 144

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 166
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 143
Specifications
A–8 975-0239-01-01
This manual for use by qualified personnel only
Mechanical Specifications
Table A-2 Xantrex XW Power System Mechanical Specifications
Model
Xantrex XW6048
120/240 60
Xantrex XW4548
120/240 60
Xantrex XW4024
120/240 60
Supported Battery Types Flooded (default), Gel, AGM, Custom
Battery bank size 100–2000 Ah
Non Volatile Memory Yes
Display Panel Status LEDs indicate AC In status, faults/warnings, equalize mode,
battery level.
Three-character display indicates output power or charge current,
fault/warning codes.
O
N/OFF and equalize button
Multiple Unit Configurations Up to 3 parallel units in 120/240 split-phase configuration
System Network Xantrex Xanbus (publish-subscribe network, no need for hubs or
special cards)
Emissions FCC Class B
Regulatory approvals UL 1741 1st Edition: 2005 Version, CSA 107.1-01
Enclosure Type NEMA Type 1 - Indoor (sensitive electronic components sealed
inside enclosure)
Rated Temperature Range
(meets all specifications)
32–104 °F (0–40 °C)
Operational Temperature
Range
-13–158 °F (-25–70 °C)
Storage Temperature Range -40–185 °F (-40–85 °C)
Inverter Dimensions
(H × W × D)
23 × 16 × 9" (580 × 410 × 230 mm)
Shipping Dimensions 28 x 22.5 x 15.5" (711 x 572 x 394 mm)
Xantrex XW Power
Distribution Panel
Dimensions (H × W × D)
30 × 16 × 8¼" (761 × 406 × 210 mm)
Depth from the wall = 8 ¾" (223 mm)
Xantrex XW Power
Distribution Panel Shipping
Dimensions
48 x 21 x 13.5" (1219 x 533 x 343 mm)
Inverter Weight 121.7 lb (55.2 kg) 118 lb (53.5 kg) 116 lb (52.5 kg)
Shipping Weight 169 lb (76.7 kg) 165 lb (75 kg) 163 lb (74 kg)