PM1000 Series Power Meters PLSED309039EN
Chapter 6 Data Communication 08/2010
50
© 2010 Schneider Electric. All rights reserved.
Parameter Settings for Different SCADA Software
The following table explains how to read the parameter VA (See ―Individual
parameter address‖ on page 53 for more information) in different Modbus
master software/PLC’s.
Table 6-3: Parameter settings
SL.
No
SCADA software
Start
Address
Function
Code
No. of
Register
Data Type
Remarks
1
ION Enterprise
43901
Internally
configured
2
Swapped Float
Direct
conversion
2
PowerLogic
SCADA
43901
Internally
configured
2
Real
Direct
conversion
3
Vijeo Citect
43901
Internally
configured
2
Real
Direct
conversion
4
Intouch
43901 F
Nil
2
Float
Direct
conversion
5
Modscan
(Master)
3901
03
HOLDING
REGISTERS
2
Floating point
Unswapped FP
mode
6
MODTEST
43901
03
Rosemount
Points -1
Float-
Rosemount
7
CIMPLICITY
43901
Nil
100
Real
Direct
conversion. The
array concept
can be used
here to poll all
the data in
single scan.
8
Allenbradly
Micrologix PLC
(Slave/Master)
43901
03-HOLDING
REGISTERS
2
Floating point
Direct
9
GE Fanuc PLC
43901
03-HOLDING
REGISTERS
2
Real
Direct
10
ABB RTU 560
(Mater)
Index-3900
03- Read
HOLDING
REGISTERS
Query
Range - 2
MFI Analog
measured
Floating value
Under sub
parameters,
―Sign and
Exponent in
First Register‖
should be
disabled
(Unchecked)
11
SEIMENS PLC
(Master)
3900
03-HOLDING
REGISTERS
2
Real
Direct
12
MOVICON
43901
Nil
2
Real
Direct
13
RSVIEW
43901
03-HOLDING
REGISTERS
2
Real
Direct
14
ABB Microscada
3900
Format 9
Interval 2
Real
Direct