AS-i Bus
Insulation Control Relay for AS-i Bus
© 2000 Schneider Electric All Rights Reserved
64
03/00
Selection
Dimensions
Recommended Wiring Schematic
Description Catalog Number
Insulation control relay for AS-i bus (supplied with an impedance adaptor) RM0PAS101
Impedance adaptor (replacement part) LA9RM401
2.99
76
2.28
58
2.64
67
1.38
35
0.59
15
3.54
90
2.28
58
Dual Dimensions: inches
mm
S3
X1
X2
X3
X4
S1
15
25
S2
18
28
+–+
R <
0 V
0 V 0 V
GND
24 Vdc
S4
To AS-i bus power supply/rest of bus
To AS-i bus master
Test
(PLC output)
Remote
reset
Reset
(PLC output)
Fault
(PLC input)
Emergency stop
Supply to actuators
Use an interposing relay if the
current consumption of the
actuators is greater than the
breaking capacity of the internal relay
(DC12: 5A/30V, DC13:1.5A/30V)
3 ohms
dc dc
RM0PAS101
AS-i
(–)
AS-i
(+)
Shd
1
3
2
(1)
The insulation control relay impedance is the same
as that of the network slave.
For correct operation, fit the impedance adaptor 1
directly on the AS-i bus supply 2, between
terminals AS-i and Shd.
Connections to ground: both the bus power supply
and the RM0PAS101 insulation relay must be
reliably connected to ground (resistance < 3 ).
(1) Maximum distance between the insulation
control relay and the AS-i bus master: 6.56 ft (2 m).
Voltage at the RM0PAS101 insulation control relay
must be between 29.5 and 31.6 Vdc.
1 Impedance adaptor LA9RM401
2 Bus power supply
3 AS-i bus master