AS-i Bus
Insulation Control Relay for AS-i Bus
63
03/00
© 2000 Schneider Electric All Rights Reserved
Test
The relay has a test feature to simulate faults. Each test sequence alternatively simulates an insulation
fault on one of the two AS-i bus polarities. The relay must respond as if the fault was authentic and
following each test, the relay must be reset as detailed above. Each subsequent test sequence checks
the other polarity of the AS-i bus (see function diagram on next page).
Two methods of testing are possible:
Locally, by pressing the TEST button.
Remotely, by a change of state of the signal between terminals S3 and S4 lasting more than 30 ms.
Function Diagram
(1)
(1)
(1)
(3)
(1)
(2)
(3)
(2)
(3)
(2)
(3)
(2)
(1)
(1)
Relay off
Supply AS-i (+) AS-i (-)
AS-i (+)
AS-i (-)
LED/OK
FAULT +
FAULT -
Reset S1 S2
Test S3 S4
Output relay
Contacts 15/18
25/28
Relay on
Input at state 0 or contact open
Input at state 1 or contact closed
LED off
LED on
(1) 30 ms minimum
(2) 15 ms
(3) 20 ms