AS-i Bus
TELEFAST SB2 Intelligent Interfaces
43
03/00
© 2000 Schneider Electric All Rights Reserved
Using TELEFAST
®
SB2 Intelligent Interfaces with Motor Starters
Associated Components
◆ Only for ABS8••: 3 contactors can be interfaced with the ASBE8S44SBB1 module (maximum accumulative current for all output channels: 3.15 A)
◆ Only for ABS8••: 3 contactors can be interfaced with the ASBE8S44SBB1 module (maximum accumulative current for all output channels: 3.15 A)
Standard Motor Starters
Rated Operational Power for
Utilization Category AC-3
DOL Non-reversing Starters Reversing Starters
Contactor
Consumption
at 24 Vdc
400/415 Vac 220/230 Vac
Disconnect/
Protector
Add-on
Auxiliary
Block
Contactors
KM1 to KM4
Disconnect/
Protector
Add-on
Auxiliary
Block
Reversing
Contactors
KM1 & KM2
Add-on
Auxiliary
Block
kW kW Catalog No. Catalog No. Catalog No. Catalog No. Catalog No. Catalog No. Catalog No. mA
0.06 – GV2M02 GV2AE20 LP1K0601BD GV2M02 GV2AE20 LP2K0601BD LA1KN11 125
0.09 0.06 GV2M03 GV2AE20 LP1K0601BD GV2M03 GV2AE20 LP2K0601BD LA1KN11 125
0.12/0.18 – GV2M04 GV2AE20 LP1K0601BD GV2M04 GV2AE20 LP2K0601BD LA1KN11 125
0.25 0.09/0.12 GV2M05 GV2AE20 LP1K0601BD GV2M05 GV2AE20 LP2K0601BD LA1KN11 125
0.37/0.55 018/0.25 GV2M06 GV2AE20 LP1K0601BD GV2M06 GV2AE20 LP2K0601BD LA1KN11 125
0.75 0.37 GV2M07 GV2AE20 LP1K0601BD GV2M07 GV2AE20 LP2K0601BD LA1KN11 125
1.1/1.5 0.55/0.75 GV2M08 GV2AE20 LP1K0601BD GV2M08 GV2AE20 LP2K0601BD LA1KN11 125
2.2 1.1 GV2M10 GV2AE20 LP1K0601BD GV2M10 GV2AE20 LP2K0601BD LA1KN11 125
3/4 1.5 GV2M14 GV2AE20 LP1K0901BD GV2M14 GV2AE20 LP2K0901BD LA1KN11 125
5.5 2.2/3 GV2M16 GV2AE20 LP1D1201BD GV2M16 GV2AE20 LP2D1201BD LA1DN11 375
7.5 4 GV2M20 GV2AE20 LP1D1801BD GV2M20 GV2AE20 LP2D1801BD LA1DN11 375
9 – GV2M21 GV2AE20 LP1D2501BD GV2M21 GV2AE20 LP2D2501BD LA1DN11 460
11 5.5 GV2M22 GV2AE20 LP1D2501BD GV2M22 GV2AE20 LP2D2501BD LA1DN11 460
15 7.5/9 GV3M40 GV2AE20 LP1D3201BD GV3M40 GV2AE20 LP2D3201BD LA1DN11 460
18.5 – GV3M40 GV2AE20 LP1D3201BD GV3M40 GV2AE20 LP2D3201BD LA1DN11 460
22 11 GV3M63 GV2AE20 LP1D5001BD – – – – 920 ◆
30 15 GV3M63 GV2AE20 LP1D6501BD – – – – 920 ◆
37 18.5/22 GV7RE80 GV7AE11 LP1D8001BD – – – – 920 ◆
High-Performance Motor Starters
Rated Operational Power for
Utilization Category AC-3
DOL Non-reversing Starters Reversing Starters
Contactor
Consumption
at 24 Vdc
400/415 Vac 220/230 Vac
Disconnect/
Protector
Add-on
Auxiliary
Block
Contactors
KM1 to KM4
Disconnect/
Protector
Add-on
Auxiliary
Block
Reversing
Contactors
KM1 & KM2
Add-on
Auxiliary
Block
kW kW Catalog No. Catalog No. Catalog No. Catalog No. Catalog No. Catalog No. Catalog No. mA
0.06 – GV2P02 GV2AE20 LP1D0901BD GV2P02 GV2AE20 LP2D0901BD LA1DN11 375
0.09 0.06 GV2P03 GV2AE20 LP1D0901BD GV2P03 GV2AE20 LP2D0901BD LA1DN11 375
0.12/0.18 – GV2P04 GV2AE20 LP1D0901BD GV2P04 GV2AE20 LP2D0901BD LA1DN11 375
0.25 0.09/0.12 GV2P05 GV2AE20 LP1D0901BD GV2P05 GV2AE20 LP2D0901BD LA1DN11 375
0.37/0.55 018/0.25 GV2P06 GV2AE20 LP1D0901BD GV2P06 GV2AE20 LP2D0901BD LA1DN11 375
0.75 0.37 GV2P07 GV2AE20 LP1D0901BD GV2P07 GV2AE20 LP2D0901BD LA1DN11 375
1.1/1.5 0.55/0.75 GV2P08 GV2AE20 LP1D1801BD GV2P08 GV2AE20 LP2D1801BD LA1DN11 375
2.2 1.1 GV2P10 GV2AE20 LP1D1801BD GV2P10 GV2AE20 LP2D1801BD LA1DN11 375
3/4 1.5 GV2P14 GV2AE20 LP1D1801BD GV2P14 GV2AE20 LP2D1801BD LA1DN11 375
5.5 2.2/3 GV2P16 GV2AE20 LP1D2501BD GV2P16 GV2AE20 LP2D2501BD LA1DN11 460
7.5 4 GV2P20 GV2AE20 LP1D2501BD GV2P20 GV2AE20 LP2D2501BD LA1DN11 460
9 – GV2P21 GV2AE20 LP1D2501BD GV2P21 GV2AE20 LP2D2501BD LA1DN11 460
11 5.5 GV2P22 GV2AE20 LP1D2501BD GV2P22 GV2AE20 LP2D2501BD LA1DN11 460
15 7.5/9 GV3M40 GV2AE20 LP1D8001BD GV3M40 GV2AE20 LP2D8001BD LA1DN11 920 ◆
18.5 – GV3M40 GV2AE20 LP1D8001BD GV3M40 GV2AE20 LP2D8001BD LA1DN11 920 ◆
22 11 GV3M63 GV2AE20 LP1D8001BD – – – – 920 ◆
30 15 GV3M63 GV2AE20 LP1D8001BD – – – – 920 ◆
37 18.5/22 GV7RE80 GV7AE11 LP1D8001BD – – – – 920 ◆
For convenience, the tables above provide references for IEC devices. The same connectivity can be done with NEMA starters and contactors. Consult the
factory for additional information.