AS-i Bus
TELEFAST SB2 Intelligent Interfaces
© 2000 Schneider Electric All Rights Reserved
38
03/00
4-Channel Modules
See curves on page 37.
Detailed operating descriptions are given in each installation guide.
State of Di bit: state of corresponding input or output. Except for ABE8S22SBB2 where the state of the outputs is the inverse of bits D2 and D3.
Type of Interface
ABE8S40SB00 ABE8R04S010 ABE8S22SBB1 ABE8S22SBB2
Function
4 inputs 4 outputs 2 inputs/2 solid state outputs
AS-i Certification
No. 113 No. 112 No. 23601
Specifications at 140 °F (60 °C)
Inputs (sensor side)
Supply voltage From the bus From the bus
Supply current limit 200 mA 200 mA
Current consumption per channel, at Un 10 mA 10 mA
Guaranteed state 1 U > / I > 11 V/6 mA 11 V/6 mA
Guaranteed state 0 U < / I < 5 V/2 mA 5 V/2 mA
Conforming to IEC 1131-2 Type 2 Type 2
Outputs (actuator side)
Supply voltage conforming to IEC 947-5-1 Ext.: 5 to 125 Vdc
Ext.: 5 to 250 Vac
Ext.: 19.2 to 30 Vdc
Maximum volt drop at In 0.5 V
Thermal rating per channel 5 A 1.4 A
Thermal rating for the common return 6 A 3 A
Rated operating current
conforming to IEC 947-5-1
AC12: 5 A
AC15: 1.5 A
DC12: 1.4 A
DC13: 1 A
Mechanical life
(in millions of operating cycles)
–20
Minimum operating current 10 mA (at 5 V) 2 mA
Maximum leakage current 0.3 mA
Overload protection Electronic
Overcurrent trip level 2 Types
Low level contact switching reliability (17 V/5 mA).
Faults per 100 million operations
–1–
Other Specifications
Current Consumption
from the Bus
"No-load" < 35 mA < 25 mA < 35 mA
With all the channels "On" < 250 mA < 100 mA < 250 mA
Internal Fuse Protection
6.3 A "quick-blow" THPC 4 A "quick-blow" FPC
Maximum Switching
Frequency
100 Hz 10 Hz "no-load"
0.5 Hz at Ie
100 Hz at input < 0.5 Hz/li
2
at output
Maximum Insulation
Voltage
Conforming to IEC 947-1 Inputs/bus
Outputs/bus 300 V 300 V
Maximum Impulse
Resistance
1.2/50 2.5 kV 2.5 kV at output
Compliance Standards
UL Listed E164866 CCN NRAQ
CSA Certified LR89150 (164581-2500005985) Class 3211 07
Indicators
Bus operational Green LED
Fault Red LED
External supply healthy Green LED
AS-i Profile
S0.0 S8.0 S3.0 S3.F
Data Bits
Bit value = 0 = 1 = 0 = 1 = 0 = 1 = 0 = 1
D0 Input 1 Output 1 Input 1 Input 1
01010 101
D1 Input 2 Output 2 Input 2 Input 2
01010 101
D2 Input 3 Output 3 Output 1 Output 1
01010 110
D3 Input 4 Output 4 Output 2 Output 2
01010 110
Parameter Bits
P0 to P3 Not used
Output Default States
Watchdog checks status of bus State 0 8S22SBB1: state 0
8S22SBB2: state 1