AS-i Bus
Inductive Proximity Sensors
© 2000 Schneider Electric All Rights Reserved
22
03/00
■ Terminal capacity: 2 x 16 AWG. Cable gland not included with sensor. Cable gland XSZPE13 to be ordered separately.
▲ Sr = Real sensing distance: sensing distance measured at rated supply voltage and at rated ambient temperature
(0.9 Sn - Sr - 1.1 Sn).
◆ Indication of detection of an object outside the correct operating zone of the sensor (see LED function table, page 23).
● Diagnostic function. Quick location of the sensor by its flashing yellow LED.
Sensors
Flush Mountable in Metal Non Flush Mountable
Nominal sensing
distance (Sn)
0.39 inches (10 mm) 0.59 inches (15 mm) 0.79 inches (20 mm)
Selection
Catalog Number
XS1M30AS101 XS7C40AS101 XS8C40AS101
Specifications
Product Certifications
AS-i No. 16901 AS-i No. 10001
Ambient Air
Temperature
Operation: -13 °F to +158 °F (-25 °C to +70 °C) Storage: -40 °F to +185 °F (-40 °C to + 85 °C)
Degree of Protection
IP 67
Shock Resistance
50 g, 11 ms conforming to IEC 68-2-27
Vibration Resistance
25 g at 55 Hz, amplitude ± 2 mm, f = 10 to 55 Hz, conforming to IEC 68-2-6
Materials
Nickel plated brass PEI PEI
Connection
Pre-cabled with moulded M12 end
connector.
Cable length: 2.62 ft (0.8 m)
Screw terminals ■ Screw terminals ■
Operating Zone
0.08 to 0.31 in (2 to 8 mm) 0.12 to 0.47 in (3 to 12 mm) 0.16 to 0.63 in (4 to 16 mm)
Repeat Accuracy
3% of Sr (2)
Differential Travel
1 to 15% of Sr ▲ 3 to 20% of Sr ▲ 3 to 20% of Sr ▲
Delays
First-up: ≤5 ms; response: ≤ 2 ms; recovery: ≤ 2 ms
Maximum Switching
Frequency
150 Hz
Indicators
Output: yellow LED
Alarm ◆: red LED
Output: yellow LED
Alarm ◆: red LED
Output: yellow LED
Alarm ◆: red LED
Power Supply
From the AS-i bus
Current Consumption
from Bus
≤35 mA
Compliance
Standards
UL Listed E164353 CCN NKCR
Data Exchange Specifications
AS-i Profile
S1.1
Data Bits (Status)
Bit value 0 1
State D0 (I) Signal “off” Signal “on”
State D1 (I) Alarm “on” (3) Alarm “off”
State D2 (I) Sensor out of service Sensor in service
Data Bits (Commands)
Command D3 (O) Not used
Parameter Bits
Bit value 0 1
Parameter P0 Not used
Parameter P1 Not used
Parameter P2 Not used
Parameter P3 Flash “on” ● Flash “off”