AS-i Bus
TSXSAY100 Master PLC Interface
13
03/00
© 2000 Schneider Electric All Rights Reserved
Module Diagnostics
The TSXSAY100 module display unit displays the status of all the I/O channels (Slave mode) and is
used for diagnostics of devices on the AS-i bus (Bus mode):
■ Defined as the time between the appearance of an input, its processing by the PLC processor, and the activation of an output on
the same slave device.
Selection
Description Protocol Number per PLC Number of I/O Catalog Number
AS-i bus master module for
Premium PLCs
AS-i
2 for 51-10
4 for 57-20
8 for 57-30
8 for 57-40
31 devices or 248 I/O
maximum
TSXSAY100
Specifications
Type of Module
TSXSAY100
Product Certifications
AS-i No. 18801, NF C 63-850
AS-i Profile
M2
Ambient Air Temperature
Operation: +32 °F to +140 °F (0 °C to +60 °C), Storage: -13 °F to +158 °F (-25 °C to +70 °C)
Degree of Protection
IP 20
Vibration Resistance
Conforming to IEC 68-2-6, Fc tests.
Shock Resistance
Conforming to IEC 68-2-27, EA tests.
Number of Connectable Slaves
31 AS-i slaves
Number of Inputs/Outputs
124 inputs and 124 outputs
Processing Times ■
Depending on the scan time of the PLC “Master Task”
Execution Time
10 ms 30 ms 60 ms
Average Processing Time
27 ms 33 ms 45 ms
Maximum Processing Time
37 ms 55 ms 80 ms
Bus Connection
By 3-way SUB-D connector
Module Power Supply
Power supply integrated on Premium PLC
(100–240 Vac, 24 Vdc)
Diagnostics
Via centralized display unit on Micro PLC or on TSXSAY100 module and the diagnostics function of PL7
Micro, PL7 Junior, and PL7 Pro software.
Compliance Standards
UL Listed E194434 CCN NRAQ
CSA Certified LR58905 Class 2252 01
0
1
8
9
16
17
24
25
2
3
10
11
18
19
26
27
6
7
14
15
22
23
30
31
4
5
12
13
20
21
28
29
Display Bus
Display I/O
0
1
8
9
16
17
24
25
2
3
10
11
18
19
26
27
6
7
14
15
22
23
30
31
4
5
12
13
20
21
28
29
Display Bus
Display I/O
0
1
8
9
16
17
24
25
2
3
10
11
18
19
26
27
6
7
14
15
22
23
30
31
4
5
12
13
20
21
28
29
Display Bus
Display I/O
Bus Mode
Displays image of the AS-i bus; each
LED 1 to 31 corresponds to a Slave
address on the bus.
Bus Mode
Displays image of the AS-i bus; each
LED 1 to 31 corresponds to a Slave
address on the bus.
Displays the address of the selected
Slave.
Slave Mode (SLV)
Displays status of I/O bits of the
selected Slave.
•
ON
TSXSAY100
AS-i Cable Connections