AS-i Bus
Intelligent Splitter Modules
47
03/00
© 2000 Schneider Electric All Rights Reserved
■ The power supplied to the module from the AS-i bus is short-circuit protected (maximum current: 100 mA).
▲ Total permissible current for the module: 2 A max.
Type
4 inputs 4 outputs
XZSDA40D3 XZSDA04D32
Environment
Product Certifications
AS-i No. 03602 AS-i No. 10301
Ambient Air Temperature
Operation: -13 °F to +158 °F (-25 °C to +70 °C)
Storage: -40 °F to +185 °F (-40 °C to +85 °C)
Degree of Protection
IP 67
Materials
PA 6- G F- F R
Connection
From the bus By connection base XZSDE••••
To the actuators
or PNP sensors
By female, 4-pin, M12 connector
Electrical Specifications
Power Supply
Module From the AS-i bus
Sensors 18 to 30 Vdc ■ -
Actuators
- From separate 24 Vdc supply, -10% to +15%
- Via connection base
Current Consumption
from the Bus
≤ 300 mA ≤ 50 mA
PNP Inputs
Maximum current for
the 2 or 4 sensors
200 mA
-
Input current - high ≥ 5 mA -
Input current - low ≤ 1.5 mA -
Input voltage - high > 10 Vdc -
Input voltage - low < 5 Vdc -
Outputs
Type - Solid state 24 Vdc
Watchdog - Default to state O (off) in the event of a communications failure
Maximum current - 2 A ▲
Short-circuit protection - Yes
Indicators
Green LED Supply
Yellow LEDs Inputs/outputs
Data Exchange Specifications
AS-i Profile
S0.0
Data Bits
Status (I)
and
Commands (O)
Bit value = 0 = 1 = 0 = 1
D0 (I): Sensor 1 signal (O): Output 1
Absent Present Off On
D1 (I): Sensor 2signal (O): Output 2
Absent Present Off On
D2 (I): Sensor 3 signal (O): Output 3
Absent Present Off On
D3 (I): Sensor 4 signal (O): Output 4
Absent Present Off On
Parameter Bits
P0 to P3 Not used