Software Release Notes
8 975-0604-01-01 Revision A
16. Changed AC coupling frequency push limits down to -5Hz.
17. Made phase_error and period_error limits to be configurable via "sync" cmd.
Defaults updated to phase=6(12°), period=250(≈ 2%).
Syntax:
SYNC return the latest readings and current limits
SYNC S # # is a number between 3 and 20. set the new phase limit
SYNC D # # is a number between 15 and 1500. set the new period limit
18. Changes made so that reconfigured AC output voltage is saved after DC
power cycle.
19. Fixed an issue where a unit may be unable to come back on after powering off
through pressing the power button. This issue only happens in multi-unit
setups where the other unit(s) is supplying the Xantrex Xanbus network power.
865-1010 (Xantrex XW4024-NA)
865-1010.01_04_00.BN0002
Build number range: 1.0.0BN18 — 1.4.0BN2
Time range: Sept 13, 2007 — Sept 25, 2008
1. Changed Line-to-Neutral Over Voltage reconnect voltage to 127.2 V (in Sell
mode).
2. Widened operating frequency range to 59.3-60.5 Hz (in Sell mode).
3. Started to use local time for all activities except logging where UTC is still
used.
4. Modified multi-unit AC qualification so that the master temporarily changes its
preferred AC source to allow transfer to the other source if all system units
have the potential to qualify the other source and one or more units cannot
qualify the preferred source.
5. Added RPO (Remote Power Off) and NLVD (No Load Voltage Derating)
features.
6. Addressed an issue where an overloaded 3 phase system could cause cross
talk on the other side of an open relay. This phantom signal was detected and
misinterpreted as a real signal. When this signal was analyzed the system
would interpret it as an AC source that was mis-wired (phase B where phase C
should have been). This mis-interpretation causes the unit to issue a F70, or a
phase configuration fault. To fix this problem, the code that caused the phase
configuration fault was adjusted to determine if the signal was real, by
ensuring that its magnitude was greater than the AC qualification threshold.
7. Changed the DC Over Voltage fault to be a power conversion fault, so that the
invert state cannot be engaged when the fault is active.
8. Fixed bug with the equalization functionality. Ensured that this functionality
was blocked in the case that the user had disabled the charger.
9. Fixed multi-unit load staggering problem, so that only one slave unit turns on
when there is a load that exceeds 60% of the rated load. Before, all slave units
would turn on but the extra unit eventually turns off.