Software Release Notes
975-0604-01-01 Revision A 19
29. Changed "FREQ" cmd so that it now accepts decimal frequency settings such
as "55.15Hz".
30. Changed AC coupling frequency push limits down to -5Hz.
31. Made phase_error and period_error limits to be configurable via "sync" cmd.
Defaults updated to phase=6(12°), period=250( 2%).
Syntax:
SYNC return the latest readings and current limits
SYNC S # # is a number between 3 and 20. set the new phase limit
SYNC D # # is a number between 15 and 1500. set the new period limit
32. Fixed an issue where a unit may be unable to come back on after powering off
through pressing the power button. This issue only happens in multi-unit
setups where the other unit(s) is supplying the Xantrex Xanbus network power.