Software Release Notes
4 975-0604-01-01 Revision A
12. Changed battery temperature compensation during charge from 10°C-40°C to
0°C-50°C
13. Implemented the "GEN SUPP PLUS" feature for the split-phase models. This
feature can be enabled via SCP. It is disabled by default. This feature allows the
neutral relay to be closed immediately upon detecting an AC over voltage (above
300V L1-L2). This is an attempt to balance L1-N and L2-N voltage to protect the
loads when AC inputs disconnect suddenly while the unit was powering an
unbalanced load. This feature helps with generators that are less than 5kW.
14. Improved charge voltage regulation in a multiunit installation where more than
one unit is charging a Gel type battery bank. Previously, the battery bank can
be over-charged and damaged due to the low impedance present in the Gel
type batteries.
15. Changed the fault-set hysteresis to 0V for F48 (DC under voltage fault) to
prevent premature fault triggering. Also changed default fault level to 46V/23V,
and recovery hysteresis to 4V/2V.
16. In order to prevent passive charging, added protection to not qualify AC if DC
voltage is below 40V for 48V system or 20V for 24V system.
17. Added protection to put unit into sleep mode if the DC voltage is below V-
LBCO for more than 24hrs to prevent draining the batteries.
18. Changed the battery over temperature fault level from 70°C to 60°C.
865-1000.01_07_00.BN0003
Build number range: 1.5.0BN11 — 1.7.0BN3
Time range: Aug 17, 2009 — July 15, 2010
1. Changes made to read input AC current:
• Split-phase models: reading the current from the primary side.
• Single-phase models: reading L1-N current.
2. Corrected "qual" cmd to display the correct GEN-L1L2 voltage.
3. Changed low battery upper limit from 26V/52V to 29V/58V on AUX output port
to give customer more flexibility.
4. Added soft start for the equalization charge stage.
5. Rebranding from Xantrex to Schneider Electric format.
6. Changed "FREQ" cmd so that it now accepts decimal frequency settings such
as "55.15Hz".
7. Changed AC coupling frequency push limits down to -5Hz.
8. Made phase_error and period_error limits to be configurable via "sync" cmd.
Defaults updated to phase=6(12°), period=250(≈ 2%).
Syntax:
SYNC return the latest readings and current limits
SYNC S # # is a number between 3 and 20. set the new phase limit
SYNC D # # is a number between 15 and 1500. set the new period limit
9. Changes made so that reconfigured AC output voltage is saved after DC
power cycle.
10. Fixed an issue where a unit may be unable to come back on after powering off
through pressing the power button. This issue only happens in multi-unit
setups where the other unit(s) is supplying the Xantrex Xanbus network power.