Software Release Notes
2 975-0604-01-01 Revision A
865-1000 (Xantrex XW6048-NA)
865-1000.01_03_00.BN0012
Build Range: 865-1000.01_00_00.BN0028 — 865-1000.01_03_00.BN0012
Time Range: Sept 26, 2007 — Jun 16, 2008
1. Changed the AC-Out-Over-Voltage fault level from 253V to 260V.
2. Changed the AC-Out-Under-Voltage from 108V to 100V.
3. Adjusted the generator support functionality such that the user can set their
generator support amps as low as zero.
4. Adjusted the peak load shaving functionality such that the user can set their
peak load shaving amps as low as zero.
5. Fixed bug where the unit was not exiting from peak load shaving and
generator support based on the user settings.
6. Increased the frequency range over which the Xantrex XW can qualify an
external source. 44Hz - 70Hz (was 52Hz to 68Hz).
7. Fixed problems where the Xantrex XW improperly blocked itself from charging
when peak load shaving was enabled, yet we were qualified on AC2.
8. Fixed situation where forced-charge bulk signal was being incorrectly ignored.
9. Added the phase-configuration-fault ( F70 ) to protect multiunit systems in the
case that an installer cross wired phase B and phase C ( 3-phase system).
10. Added a wiring protection for 3-phase multi-unit systems. The system will
issue a fault if phase B and phase C wired in reverse.
11. Fixed a preferred-source issue with multi-unit functionality. Prior to fix a system
could sit indefinitely in an inverting state despite there being a valid AC source.
12. Adjusted F69 such that it is auto-escalating. It was previously a manual fault,
which meant that the user had to take action when it occurred. However, false
trips were detected in the field and to respond to customer concerns the fault
behavior was changed.
13. Added a time-to-clear counter on the DUI for the user to see how long they
have to wait before they can sell power back to the grid.
14. Fixed bug with the equalization functionality. Ensured that this functionality
was blocked in the case that the user had disabled the charger.
15. Updated to the latest Xantrex Xanbus™ release.
16. Added support for 3-phase multi-unit operation.
865-1000.01_05_00.BN0011
Build number range: 1.3.0BN12 — 1.5.0BN11
Time range: June 16, 2008 — Aug 17, 2009
1. Fixed problem where system would lock up after multiple adjustments of support
amps from 0 to 10 to 0 during Peak Load Shaving and Generator Support.
2. Moved Sell Enable/Disable parameter to non-volatile memory so that its value
is kept after power off.