Planning Instruction 66571758GB0 Fire Detection 6
Schneider Electric Pelco Finland Oy
Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571758GB0 49 2011
© 2009 Schneider Electric. All rights reserved.
2. General description of the FX 3NET system
2.1 Standalone FX 3NET or FXL 3NET fire detection system
Application areas
Protectable area up to 15,000 m²
(512 addresses – EN54)
Business and office buildings
Industrial sites
Lodging houses
Service centres
Health and nursing centres
Educational buildings
Main features
The modular design of the FX 3NET and FXL
3NET 2, 4, 6, or 8 loop control panel offers a
competitive solution for small and medium sized
projects. The address capacity of the detection
circuits also offers flexibility for cabling, thus
saving costs in installation work.
A wide range of intelligent detectors provides
solutions for all applications. In addition,
conventional detectors can be connected to
interface modules, making an upgrade of a former
conventional system flexible.
In many tests, the high-sensitive laser detectors
have proved to be even more efficient than the
aspiration detection systems often used in, for
example, computer rooms.
The I/O-modules are economical and save space
in installation, and provide monitoring and control
functions.
With the extensive configuration software, all
addresses and many control functions of the panel
can be adopted for the requirements of the
installation site.
The communication capability makes it possible to
connect a standard printer and additional alarm
display panels.
FX 3NET and FXL 3NET standalone system
metrics
2 ... 8 addressable detection circuits
159 intelligent detectors + 159 I/O-modules per
detection circuit
250 detection zones
512 detectors and manual call points / EN54
regulation
2,544 addresses totally
17 Ah (internal in FX), 34 Ah (external), 51 Ah
(external) or 68 Ah (external) batteries
1.0 A total load in normal condition and 4.0 A total
load in alarm condition
2.2 Standalone FXM 3NET fire detection system
Main features
The FXM control panel offers the same features as
the FX and FXL panels, but in a smaller format, with
a smaller power supply and with less space for I/O
controllers.
Application areas
Protectable area up to 15,000 m²
(512 addresses – EN54)
Industrial sites
Lodging houses
Elderly service centres
Day care centres
Educational buildings
FXM 3NET standalone system metrics
1 ... 4 addressable detection circuits
159 intelligent detectors + 159 I/O-modules per
detection circuit
250 detection zones
512 detectors and manual call points / EN54
regulation
1272 addresses totally
12 Ah (internal) or 34 Ah (external) battery capacity
0.5 A total load in normal condition and 2.2 A total
load in alarm condition
Note!
When the INFO serial communication is used, the maximum address capacity per detection circuit is
214: lower address range 1...159 + higher address range 201...255.