Planning Instruction 66571758GB0 Fire Detection 23
Schneider Electric Pelco Finland Oy
Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571758GB0 49 2011
© 2009 Schneider Electric. All rights reserved.
6.4 FX control groups
Note!
See the document “Configuration data”.
Note!
See the user manual of the WinFX3Net configuration tool.
The concept of control groups in an FX panel is a way of grouping the various inputs of the panel to facilitate the
activation of outputs. The control groups are defined separately from the detection zones.
‘Control groups’ goes hand in hand with ‘events’. There are two kinds of events: input events and output events.
Input events are the type of signals that the control logic reacts to for example, when a detector gives a fire signal,
we say that the input event is a fire event. Output events are events activated (triggered) by the logic. Certain input
events have corresponding output events for example, a fire input event corresponds to an alarm device output
event.
999 specific control groups, one local (general) control group and one general control group are defined. In this
document, and in the configuration tool, these are identified with the numerical values 1 ... 999 and the words
'Local' and ‘General’, respectively.
In an FX 3NET system, the 999 control groups are split into two ranges: local and shared (over the network). The
split point is by default at 100, meaning that the local control groups are 1 ... 100 and the shared control groups are
101 ... 999. The split point can be changed for each panel with the configuration tool. Input events for the control
groups in the local range are seen only by the panel where the event occurs. Input events for the control groups in
the shared range are seen by all seeing panels.
There are nine different control groups to be defined for a certain input event. The table below describes the main
functional options of control groups.
Control
group
Functional options
Ctrl A
Ctrl B
For all input event types
For all inputs: panel and addresses
Default split point 100 local/shared
For phased evacuation (6.4.3)
For delayed alarm (6.4.4)
CG1 + D
CG2 + D
CG3 + D
CG4 + D
CG5 + D
CG6 + D
CG7 + D
For address fire input
For fire outputs
Default split point 100 local/shared
Delayed outputs (6.4.2)
Delay 0 ... 60 minutes with 1 second step